TM 5-6350-280-23&P
CHAPTER 2
INSTALLATION
SUBJECT INDEX
PAGE
SECTION I
SITE AND SHELTER REQUIREMENTS ........................................................................
2-1
2.1
SITE REQUIREMENTS.................................................................................................
2-1
2.1.1
System Planning...........................................................................................................
2-1
2.1.2
Power Requirements.....................................................................................................
2-1
2.1.3
Installed Equipment.......................................................................................................
2-1
2.1.4
AMG Equipment Location Requirements ........................................................................
2-1
2.1.5
Engineering Support .....................................................................................................
2-2
SECTION II
SERVICE UPON RECEIPT OF MATERIEL ...................................................................
2-2
2.2
UNPACKING ................................................................................................................
2-2
2.2.1
Unpacking Alarm-Monitor Group (AMG) OA-9431/FSS-9(V)............................................
2-2
2.2.2
Unpacking J-SIIDS Equipment .......................................................................................
2-2
2.2.3
Unpacking IBM-PC\AT Compatible Computer Equipment ................................................
2-2
2.3
CHECKING UNPACKED EQUIPMENT..........................................................................
2-2
2.4
PROCESSING UNPACKED EQUIPMENT.....................................................................
2-2
2.5
ASSEMBLY OF EQUIPMENT........................................................................................
2-2
2.5.1
Uninterruptible Power Supply (UPS) Battery Installation ..................................................
2-2
2.5.2
Communications Circuit Card Assembly (CCA) Assembly ...............................................
2-2
2.6
INSTALLATION INSTRUCTIONS ..................................................................................
2-3
2.7
STORAGE....................................................................................................................
2-4
SECTION I SITE AND SHELTER REQUIREMENTS
2.1 SITE REQUIREMENTS.
2.1.1 System Planning. The responsibility of the AMG initial installation rests with the installation commander and
engineering staff. General information for system planning is provided in chapter 2, Section I of TM 5-6350-264-14-1.
Installation of the software requires a password to be entered and must be performed by designated personnel. The
remainder of this chapter is for information only and recommended special site requirements unique to the AMG.
2.1.2 Power Requirements. Power requirements are provided in chapter 2, Section I of TM 5-6350-264-14-1. The
Uninterruptible Power Supply for the AMG can operate on any of the following: 100, 120, 230, or 240 Vac at either 50 or
60 Hz power. The UPS requires an independent fused line rated at 30 amperes (amps) for 120 Vac or 16 amps for 240
Vac at the distribution panel. Each site must provide all power cables.
2.1.3 Installed Equipment. The site must have the Joint-Service Interior Intrusion Detection System (J-SIIDS) equipment
installed and user purchased IBM-PC/AT compatible computer, keyboard, color monitor, and dot matrix printer installed.
Refer to TM 5-6350-264-14-1 for detailed installation of the J-SIIDS.
2.1.4 AMG Equipment Location Requirements.
2.1.4.1 Uninterruptible Power Supply (UPS) Location. The UPS must be located on flooring that supports a minimum
of 669 pounds (lbs) (304 Kg). Environmental temperature must be maintained between 32 to 77 F (0 to 25 C). The
power source must be capable of providing a single 30 ampere (amp) circuit breaker that is dedicated to the operation of
the UPS. The UPS provides all power requirements of the CMA and computer. Two power cables (not provided) must be
routed from the UPS to the locations of the Converter Multiplexer Assembly (CMA) and computer. In addition, the UPS
must be located within 100 feet (ft) of the CMA because of restriction of the UPS cable.
2-1