1.12 EQUIPMENT DATA.
This paragraph provides performance data, including numerical and other specification related data. It summarizes the
specific capabilities and limitations of the equipment and other critical data needed.
1.12.1 Uninterruptible Power Supply (UPS) Equipment Data. The data for the UPS are as follows:
Input:
Voltage:
100, 120, 230, or 240 V ac at 60 Hz
or
100, 120, 230, or 240 V ac at 50 Hz
Output:
Power Rating:
1500 Volt amps
Voltage:
120 V ac at 60 Hz ± 3 Hz
Waveform:
True Regulated Sine Wave
Harmonic Distortion:
Less than 5% total
Operating Temperature:
320 to 1040 F (00 to 400C)
Battery Backup:
At least four hours
Weight:
with batteries:
670 lbs (304 kg)
without batteries:
208 lbs (094 kg)
Batteries:
Weight
77 lbs (33 kg)
Nominal Voltage:
12 V dc
Charging Voltage:
13.5 to 13.6 V dc at 770 F (250 C)
Max Charger Current:
22 amps
Discharge Current:
351 amps to 1.75 volt/cell
Internal Resistance
3.9 Megaohms
(Charge)
Operating Temperature:
320 to 800 F (00 to 450 C)
Rated
110 Amp/hour
Total Required
Six (sealed cell)
Dimensions in inches:
Height
Width
Depth
45.25 (1.15 m)
17 (43.18 cm)
21 (53.34 cm)
1.12.2 Converter-Multiplexer Assembly (CMA) Equipment Data. The data for the CMA is as follows:
Weight:
250 lbs (114 Kg)
Dimensions in inches:
Height
Width
Depth
42.5 (1.08 m)
22.5 (57.15 cm)
31.5 (80.01 cm)
Change 1 1-3