TM 5-6350-280-10
Table 1-4. Features
Feature
Purpose
<Esc>
Clears a selected area from the command
line. Also clears operator input for
Area:" or "Password."
Automatic
The AMG Monitor program automatically
Synchronization
synchronizes with the J-SIIDS data
transmitters communication, eliminating
the need for a maintainer to press the
resynchronization button in the J-SIIDS
control unit. This also eliminates the
need for code plugs at the status
monitoring equipment.
CHANGE"
On the print out, this is printed with an
area number or module number and
indicates a status change occurred on that
area or module.
ACK"
On the print out, this is printed with an
area number or module number and
indicates that a status change was
acknowledged for that area or module.
RESET"
On the print out, this is printed with an
area number or module number and
indicates that an alarm was reset for
that area or module.
"*"
The purpose of the asterisk is to
identify status changes such as CHANGE",
ACK", or RESET' for an area or module.
COM-norm-000"
On the print-out, this is printed for an
area when the communication with the area
is good.
COM-FAIL-xyz"
On the print out, this is printed for an
area when there is a communication
problem. x", "y" and z" can each be
either a 0" or 1." When set to 1,
represents a loss of synchronization;
"y" represents a loss of data signal; "z"
represents a line fault (low signal
level).
"Resync-M"
On the print out, this is printed for an
area when the resynchronization button
was pressed at the J-SIIDS control unit
(manual resync).
1-8